The P376 digital output slice connects the binary control signals from the Motion Coordinator to the machine’s output devices, such as relays, contactors, valves, lamps etc. at 24V dc.

All 16 outputs are source (PNP) type and have electrical isolation. Outputs and power connection are via 2 x single-row plug-in screw terminal blocks. The Flexslice module indicates the output signal states via LEDs.

Module current consumption (EBUS 5V)110mA max
Number of Digital Outputs
16 (2 banks of 8)
Power supply requirement
24V (+/-20%) DC
Load type
Resistive, inductive and capacitive
“ON” time110us (10% to 90%)
“OFF” time
210us (90% to 10%)
Max. Output current

0.5A per channel

4A per bank of 8 Outputs

Short−Circuit Protection
1.4A typ per output
Over voltage Protection
Yes
Reverse Voltage ProtectionYes
Power Supply 24V / 1.5W
Isolation1KV
MountingDIN rail mount
Size (w x d x h) mm15 x 147 x 107
Weight145g
ConnectorsPush-in wiring terminals
EMCEN61000-6-2 (2005) Industrial Noise Immunity/ EN61000-6-4 (2007) Industrial Noise Emissions.